Oriel — AI & technology worth noticing, every day.

Don't bother patching: multiple remote code execution vulnerabilities in Danfoss AK-SM800A

Web page · https://midnightblue.nl/blog/multiple-rce-danfoss-aksm800a

First seen by Oriel on .

AI summary

This security research reports six pre-authentication remote code execution vulnerabilities in Danfoss AK-SM800A firmware, including the latest 5.3.2, and recommends removing internet exposure rather than relying on patching.

  • Researchers found six stack-based buffer overflows affecting AK-SM800A versions through 5.3.2, with potential full device takeover, persistence, or persistent denial of service.
  • The firmware runs ARM binaries in a custom Yocto-based Linux distribution, while externally reachable CGI handlers and sm_app use hundreds of strcpy calls.
  • sm_app lacks stack canaries and PIE, runs as root, and an unauthenticated overflow was demonstrated as full remote code execution.
  • Strict session control fences off most web attack surface, but sm_fcgi_app contains another pre-authentication memory corruption that can also become RCE.
  • The researchers withhold exploit details during coordinated disclosure and recommend VPNs, private APN, or highly restrictive IP whitelisting ACLs.

#embedded systems #ics security #remote code execution #danfoss

Generated by gpt-5.6-sol. Check the original for details.

Metric trends

Last 30 days · Up to 120 recorded samples per source and metric, with reposts kept separate · First and latest retained

Points

Score reported by the source.

  • Hacker News: 20, latest observation ; +16 over observed period since
  • Lobsters: 9, latest observation ; +6 over observed period since

Comments

Comment count reported by the source.

  • Hacker News: 6, latest observation ; +6 over observed period since
  • Lobsters: 1, latest observation ; 0 over observed period since

Aliases

SourceExternal IDURL
Hacker News50455031https://www.midnightblue.nl/blog/multiple-rce-danfoss-aksm800a Read discussion
Lobstersrpd05thttps://www.midnightblue.nl/blog/multiple-rce-danfoss-aksm800a Read discussion